Rockwell Automation 284 ArmorStart User Manual User Manual

Page 381

Advertising
background image

Bulletin 283 CIP Information

C-9

Standard Distributed Motor
Controller Output (Consumed)
Assemblies

Table C.21 Instance 3 is the required output (consumed) assembly defined in

the DeviceNet Motor Starter Profile

Table C.22 Instance 160 is the default output (consumed) assembly for

Standard Distributed Motor Controllers

Table C.23 Instance 162 is the standard output (consumed) assembly with

Network Inputs

Standard Distributed Motor Controller
Input (Produced) Assemblies

Table C.24 Instance 52 is the required input (produced) assembly defined in

the DeviceNet Motor Starter Profile

Table C.25 Instance 161 is the default input (produced) assembly for

Standard Distributed Motor Controllers

For Bulletin 283A only.

Instance 3 — ODVA Starter

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Run Fwd

Instance 160 — Default Consumed Standard Distributed Motor Controller

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

User Out

B

User Out

A

Fault

Reset

Run Fwd

Instance 162 — Standard Consumed Starter with Network Inputs

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

User Out

B

User Out

A

Fault

Reset

Run Fwd

1

Net In 8

Net In 7

Net In 6

Net In 5

Net In 4

Net In 3

Net In 2

Net In 1

2

Net In 16 Net In 15 Net In 14 Net In 13 Net In 12 Net In 11 Net In 10 Net In 9

Instance 52 — ODVA Starter

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Running

Fault

Instance 161 — Default Produced Standard Distributed Motor Controller

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Ready

Running

Fwd

Warning

Tripped

1

140M On

HOA

Stat.

User In 3 User In 2 User In 1 User In 0

Reserved

Reserved

Reserved

Reserved