Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-39

Jog Accel/Decel
Sets the acceleration and deceleration time when a jog command is issued.

Parameter Number

179

Related Parameters

178, 151, 152, 153, 154

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 sec

Minimum Value

0.1

Maximum Value

600.0

Default Value

10.0

DC Brake Time
Sets the length of time that DC brake current is injected into the motor. Refer to
Parameter 181 DC Brake Level.

Parameter Number

180

Related Parameters

137, 181

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 sec

Minimum Value

0.0

Maximum Value

99.9

(Setting of 99.9 = Continuous)

Default Value

0.0

DC Brake Level
Defines the maximum DC brake current, in amps, applied to the motor when
Parameter 137 (Stop Mode) is set to either Ramp or DC Brake.

Parameter Number

181

Related Parameters

137, 180

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 A

Minimum Value

0.0

Maximum Value

Drive rated amps X 1.8

Default Value

Drive rated amps X 0.05

ATTENTION

!

• If a hazard of injury due to movement of equipment or
material exists, an auxiliary mechanical braking device must
be used.
• This feature should not be used with synchronous or
permanent magnet motors. Motors may be demagnetized
during braking.