5-46

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

Figure 5.4

Clear a Type 1 Fault and Restart the Drive

1. Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.

2. Set Parameter 193 (AutoRstrt Delay) to a value other than 0.

PWM Frequency
Sets the carrier frequency the PWM output waveform. The Figure 5.4 provides
derating guidelines based on the PWM frequency setting.

Parameter Number

191

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.l Hz

Minimum Value

2.0 Hz

Maximum Value

16.0 Hz

Default Value

4.0 Hz

Auto Rstrt Tries
Set the maximum number of times the drive attempts to reset a fault and restart.

Parameter Number

192

Related Parameter

155, 193

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1

Minimum Value

0

Maximum Value

9

Default Value

0