Rockwell Automation 284 ArmorStart User Manual User Manual

Page 297

Advertising
background image

Troubleshooting

14-3

Table 14.1 Fault LED Indications for Bulletin 280 and 281 ArmorStart

Distributed Motor Controllers

➊Not available on the Bulletin 280A/281A.

Blink Pattern

Definitions

Possible Causes or Remedies

1

Short Circuit

The motor circuit protector has tripped, or the internal wiring protection
algorithm has detected an unsafe current range. Try to reset the protector if
tripped. If the condition continues, check the power wiring. This fault cannot
be disabled.

2

Overload Trip

The load has drawn excessive current and based on the trip class selected,
the device has tripped. Verify that the load is operating correctly and the
ArmorStart is properly set-up. This fault cannot be disabled.

3

Phase Loss

The ArmorStart has detected a missing phase. Verify that three-phase
voltage is present at the line side connections. This fault can be disabled
and is disabled by default.

4

Reserved

Not Used

5

Reserved

Not Used

6

Control Power

The ArmorStart has detected a loss of the control power voltage or blown
control power fuse. Check control voltage, wiring, and proper polarity.
Replace control voltage fuse if necessary. This fault can be disabled and is
disabled by default.

7

I/O Fault

This error indicates a shorted sensor, shorted input device, or input wiring
mistakes or a blown output fuse. If this fault occurs, the offending problem
should be isolated or removed prior to restarting the system. This fault can
be disabled and is disabled by default.

8

Over Temperature

Indicates that the operating temperature has been exceeded. This fault
cannot be disabled.

9

Phase Imbalance

The ArmorStart has detected a voltage imbalance. Check the power system
and correct if necessary. This fault can be disabled and is disabled by
default.

10 ➊

DNet Power Loss

DeviceNet™ power has been lost or has dropped below the 12 volt
threshold. Check the state of the network power supply and look for
DeviceNet media problems. This fault can be disabled and is disabled by
default.

11

Reserved

Not Used

12

Reserved

Not Used

13

EEPROM Fault

This is a major fault, which renders the ArmorStart inoperable. Possible
causes of this fault are transients induced during EEprom storage routines.
If the fault was initiated by a transient, power cycling should clear the
problem; otherwise, replacement of the ArmorStart may be required. This
fault cannot be disabled.

14

Hardware Fault

This fault indicates that a serious hardware problem exists. Check for a
base/starter module mismatch. If no mismatch exists, the ArmorStart may
need to be replaced. (Hdw Flt is the factory-enabled default setting.) This
fault cannot be disabled.

Advertising
This manual is related to the following products: