Rockwell Automation 284 ArmorStart User Manual User Manual

Page 389

Advertising
background image

Bulletin 283 CIP Information

C-17

Four instances of the Discrete Output Point Object are supported. The
following table summarizes the DOP instances:

Table C.39 Discrete Output Point Object Instance Attributes

All instances contain the following attributes.

For DOP instances 1 and 2, attributes 113 and 114 have “Get” only

access, and their values are always 0.

The following common services are implemented for the Discrete
Output Point Object:

Table C.40 Discrete Output Object Common Services

Instance ID

Name

Alternate

Mapping

Description

1

Run Fwd Output

0029 – 01 – 03

Run Forward output. For all starter

types, this output is hard wired from

the ArmorStart CPU to the actuator

2

3

User Output A

none

These are the 2 ArmorStart user

outputs.

4

User Output B

none

Attribute ID

Access Rule

Name

Data Type

Value

3

Get

Value

BOOL

0=OFF, 1=ON

5

Get/Set

Fault Action

BOOL

0=Fault Value attribute, 1=Hold Last State

6

Get/Set

Fault Value

BOOL

0=OFF, 1=ON

7

Get/Set

Idle Action

BOOL

0=Fault Value attribute, 1=Hold Last State

8

Get/Set

Idle Value

BOOL

0=OFF, 1=ON

113

Get/Set ➊

Pr Fault Action

BOOL

0=Pr Fault Value attribute, 1=Ignore

114

Get/Set ➊

Pr Fault Value

BOOL

0=OFF, 1=ON

115

Get/Set

Force Enable

BOOL

0=Disable, 1=Enable

116

Get/Set

Force Value

BOOL

0=OFF, 1=ON

Service

Code

Implemented for:

Service

Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single