Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-41

Table 6.6 Boost Select Options

Figure 6.1

Options

Description

0

Custom V/Hz

Variable Torque (Typical fan/pump

curves)

1

30.0, VT

2

35.0, VT

3

40.0, VT

4

45.0, VT

5

0.0 no IR

Constant Torque

6

0.0

7

2.5, CT (Default for 5 Hp/4.0 kW Drive)

8

5.0, CT Default

9

7.5,CT

10

10.0,CT

11

12.5,CT

12

15.0,CT

13

17.5,CT

14

20.0,CT

% Parameter 132 (Motor NP Hertz)

% Parameter 131 (Motor NP V

olts)

1/2 (Motor NP Volts)

Settings

5...14

0

50

100

50

100

4

1

2

3

1/2

(Motor NP Hertz)