Rockwell Automation 284 ArmorStart User Manual User Manual

Page 268

Advertising
background image

10-4

Using DeviceLogix™

14. From the toolbar, Click on the “Discrete Output” button and

select “Run Fwd” from the pull-down menu. Run Fwd is the
relay controlling the coil of the contactor. Click OK.

15. Move the cursor into the grid and place the Output to the right of

the RSL function block.

16. Connect the output of the “RSL” function block to Run Fwd.

17. Click on the “Verify” button located in the toolbar or select

“Logic Verify” from the “Tools” pull-down menu.

18. Click on the “Edit” button to toggle out of edit mode if online

with a device.

19. Go to the pull-down menu in the right corner of the toolbar and

select “Download”.

20. Note: Ensure that the PLC key switch is in the Program position.

If in any other position, the download will not occur and an error
will be generated.

21. Press “OK” when told the download was successful.

22. Now from the same pull-down menu select “Logic Enable On.”

23. The ArmorStart is now programmed and the logic is Active.