Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-49

Fault Clear

Resets a fault and clears the fault queue. Used primarily to clear a fault over
network communications.
0 = Ready/Idle (Default)
1 = Reset Fault
2 = Clear Buffer (Parameters 107…109 [Fault x Code])

Parameter Number

200

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

2

Default Value

0

Program Lock
Protects parameters against change by unauthorized personnel.
0 = Unlocked
1 = Locked

Parameter Number

201

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Testpoint Sel
Used by Rockwell Automation field service personnel.

Parameter Number

202

Related Parameters

119

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1 Hex

Minimum Value

0

Maximum Value

FFFF

Default Value

400

Comm Data Rate
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.

Parameter Number

203

CommNode Addr
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.

Parameter Number

204

Comm Loss Action
Selects the drive’s response to a loss of the communication connection or excessive
communication errors.
0 = Fault (Default)
Drive will fault on an F81 Comm Loss and coast to stop
1 = Coast Stop
Stops drive via coast to stop
2 = Stop
Stops via Parameter 137 (Stop Mode) setting
3 = Continu Last
Drive continues operating at communication commanded speed saved in RAM

Parameter Number

205

Related Parameters

115, 137, 206

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

3

Default Value

0

Stop drive before changing this parameter.