6-40

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

Figure 6.2

DB Resistor Sel

Enables/disables external dynamic braking.

Parameter Number

182

Related Parameters

137

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1

Minimum Value

0

Maximum Value

99

Default Value

0

S Curve %
Sets the percentage of acceleration or deceleration time that is applied to ramp as S
Curve. Time is added, half at the beginning and half at the end of the ramp.

Parameter Number

183

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1%

Minimum Value

0

Maximum Value

100

Default Value

0% disabled

Stop drive before changing this parameter.

Setting

Min./Max.

0

Disabled

1

Normal RA Res (5% Duty Cycle)

2

No Protection (100% Duty Cycle)

3…99

x% Duty Cycle Limited (3…99% of Duty Cycle)

Boost Select
Sets the boost voltage (% of Parameter 131 [Motor NP Volts]) and redefines the Volts
per Hz curve. Active when Parameter 225 (Torque Perf Mode) = 0V/Hz Drive may
add additional voltage unless Option 5 is selected.

See Table 6.6 for details

Parameter Number

184

Related Parameters

104, 131, 132, 185, 186, 187,

225

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

14

Default Value

8