Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

Advanced Program Group

151 (Digital In 1 SEL)
152 (Digital In 2 SEL)

Selects the function for the digital inputs.

See Table 5.B for details

Parameter Number

151, 152

Related Parameters

112, 114, 138…140, 167,

168, 170…173, 178, 179

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

26

Default Value

4

Table 5.B Digital Inputs Options

Options

Description

0

Not Used

Terminal has no function but can be read over network communication via Parameter 114 (Dig In Status).

1

Acc & Dec2

When active, Parameter 167 (Accel Time 2) and Parameter 168 (Decel Time 2) are used for all ramp rates
except Jog.

Can only be tied to one input.

2

Jog

When input is present, drive accelerates according to the value set in Parameter 179 (Jog Accel/Decel) and
ramps to the value set in Parameter 178 (Jog Frequency).

When the input is removed, drive ramps to a stop according to the value set in Parameter 179 (Jog Accel/
Decel).

A valid Start command will override this input.

3

Aux Fault

When enable, an F2 Auxiliary Input fault will occur when the input is removed.

4

Preset Freq

(Parameters 151
and 152 Default)

Refer to Parameters 170…173 and 174…177.

5…25

Not Used

Reserved

26

Anlg Invert

Option not valid for Bulletin 284 ArmorStart Distributed Motor Controller

Stop drive before changing this parameter.