Bulletin 280/281 CIP Information

B-25

Control Supervisor Object -CLASS
CODE 0x0029

No class attributes are supported.

The following instance attributes are supported:

A single instance (instance 1) of the Control Supervisor Object will
be supported.

Table B.50 Control Supervisor Instance Attributes

Attribute ID

Access Rule

Name

Data Type

Value

3

Get/Set

Run 1

BOOL

These Run outputs also map to DOP instances 1

and 2.

*4

Get/Set

Run 2

BOOL

7

Get

Running 1

BOOL

Status of RUN FWD contact

*8

Get

Running 2

BOOL

Status of RUN REV contact

9

Get

Ready

BOOL

Device not faulted

10

Get

Tripped

BOOL

Device faulted

12

Get/Set

Fault Reset

BOOL

0->1 = Trip Reset

100

Get/Set

Keypad Mode

BOOL

0=Maintained; 1=Momentary

101

Get/Set

Keypad Disable

BOOL

0=Not Disabled; 1=Disabled

115

Get

Warning Status

WORD

Bits 0-4 = reserved

Bit 5 = CP Warning

Bit 6 = IO Warning

Bit 7 = reserved
Bit 8 = reserved

Bit 9 = DN Warning

Bits 10-12 = reserved

Bit 13 = HW Warning

Bits 14-15 = reserved

124

Get/Set

Trip Enable

WORD

Bit enumerated trip enable word

130

Get/Set

Trip Reset Mode

BOOL

0=manual; 1=auto

131

Get/Set

Trip Reset Level

USINT

0 – 100%; default = 75

151

Get

Base Enclosure

WORD

Bit 0 = IP67

Bit 1 = NEMA 4x

Bits 2-15 reserved

152

Get

Base Options

WORD

Bit 0 = Output Fuse

Bit 1 = Safety Monitor

Bit 2 = CP Fuse Detect

Bits 3-7 = Reserved

Bit 8 = 10A Base
Bit 9 = 25A Base

Bit 10-15 = Reserved

153

Get

Wiring Options

WORD

Bit 0 = Conduit

Bit 1 = Round Media

Bits 2-15 = Reserved

154

Get

Starter Enclosure

WORD

Bit 0 = IP67

Bit 1 = NEMA 4x

Bits 2-15 reserved

155

Get

Starter Options

WORD

Bit 0 = Full Keypad

Bit 1 = Safety Monitor

Bits 2-15 reserved

156

Get

Last Pr Trip

UINT

See Parameter 61