Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-45

Clear a Type 1 Fault and Restart the Drive

1. Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.

2. Set Parameter 193 (AutoRstrt Delay) to a value other than 0.

Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault
without Restarting the Drive

1. Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.

2. Set Parameter 193 (AutoRstrt Delay) to 0.

Auto Rstrt Tries
Set the maximum number of times the drive attempts to reset a fault and restart.

Parameter Number

192

Related Parameter

155, 158, 161, 193

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1

Minimum Value

0

Maximum Value

9

Default Value

0

ATTENTION

!

Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not
use this function without considering applicable local,
national, and international codes, standards, regulations, or
industry guidelines.

Auto Rstrt Delay
Sets time between restart attempts when Parameter 192 (Auto Rstrt Tries) is set to a
value other than zero.

Parameter Number

193

Related Parameters

192

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 sec

Minimum Value

0.0

Maximum Value

300.0 sec

Default Value

1.0 sec