Frequency time – Rockwell Automation 284 ArmorStart User Manual User Manual

Page 235

Advertising
background image

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-61

EM Brk Off Delay
Sets the time the drive will remain at minimum frequency before ramping to the
commanded frequency and energizing the brake coil relay when Parameter 137 (Stop
Mode) is set to option 8 or 9.

Parameter Number

260

Related Parameters

137

Access Rule

GET/SET

Data Type

UNIT

Group

Advanced Setup

Units

0.01 sec

Minimum Value

0.01 sec

Maximum Value

10 sec

Default Value

0.0 sec

EM Brk On Delay
Sets the time the drive will remain at minimum frequency before stopping and de-
energizing the brake coil relay when Parameter 137 (Stop Mode) is set to option 8 or
9.

Parameter Number

261

Related Parameters

137

Access Rule

GET/SET

Data Type

UNIT

Group

Advanced Setup

Units

0.01 sec

Minimum Value

0.01 sec

Maximum Value

10.00 sec

Default Value

0.0 sec

MOP Reset Sel
Sets the drive to save the current MOP Reference command.
0 = Zero MOP Ref
This option clamps Parameter 169 (Internal Freq) at 0.0 Hz when drive is not running.
1 = Save MOP Ref (Default)
Reference is saved in Parameter 169 (Internal Freq).

Parameter Number

262

Related Parameters

169

Access Rule

Get/Set

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Frequency

Time

Minimum Freq

260 [EM Brk Off Delay]

261 [EM Brk On Delay]

Stop

Commanded

Start

Commanded

EM Brk

De-Energized (On)

Drive Stops

EM Brk
Energized (Off)

Ramp Accel

Ramp Decel