Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-45

Figure 5.3 Overload Trip Curves

Maximum Voltage
Sets the highest voltage the drive will output.

Parameter Number

188

Related Parameters

104

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1V AC

Minimum Value

20V AC

Maximum Value

Drive Rated Volts

Default Value

Drive Rated Volts

Current Limit
Maximum output current allowed before current limiting occurs

Parameter Number

189

Related Parameters

133

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 A

Minimum Value

0.1 A

Maximum Value

Drive rated amps X 1.8

Default Value

Drive rated amps X 1.5

Motor OL Select
Drive provides Class 10 motor overload protection. Setting 0…2 select the derating

factor for I

2

t overload function.

0 = No Derate
1 = Min. Derate
2 = Max. Derate

Parameter Number

190

Related Parameters

132

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1

Minimum Value

0

Maximum Value

2

Default Value

0

% of P132 (Motor NP Hertz)

% of P132 (Motor NP Hertz)

% of P132 (Motor NP Hertz)

% of P133 (Motor OL Current)

% of P133 (Motor OL Current)

% of P133 (Motor OL Current)