Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-43

Brake Voltage
Sets the frequency where break voltage is applied when Parameter 184 (Boost
Select) = 0 Custom V/Hz and Parameter 225 (Torque Perf Mode) = 0V/Hz.

Parameter Number

186

Related Parameters

131, 132, 134, 135, 184, 185,

187, 188, 225

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1.1%

Minimum Value

0.0%

Maximum Value

100.0%

Default Value

25.0%

Brake Frequency
Sets the frequency where break frequency is applied when Parameter 184 (Boost
Select) = 0 Custom V/Hz and Parameter 225 (Torque Perf Mode) = 0V/Hz.

Parameter Number

187

Related Parameters

131, 132, 134, 135, 184, 185,

186, 188, 225

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 Hz

Minimum Value

0.0 Hz

Maximum Value

400.0 Hz

Default Value

15.0 Hz

Maximum Voltage
Sets the highest voltage the drive will output.

Parameter Number

188

Related Parameters

104, 185, 186, 187

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1V AC

Minimum Value

20V AC

Maximum Value

Drive Rated Volts

Default Value

Drive Rated Volts

Current Limit 1
Maximum output current allowed before current limiting occurs

Parameter Number

189

Related Parameters

133, 218

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 A

Minimum Value

0.1 A

Maximum Value

Drive rated amps X 1.8

Default Value

Drive rated amps X 1.5