Rockwell Automation 284 ArmorStart User Manual User Manual

Page 355

Advertising
background image

Bulletin 280/281 CIP Information

B-11

Instance 2 is the Predefined Group 2 Connection Set Polled I/O
Message Connection. The following instance 2 attributes are
supported:

Table B.29 Connection Object Instance 2 Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0=nonexistant

1=configuring
3=established

4=timed out

2

Get

Instance Type

USINT

1= I/O Connection

3

Get

Transport Class Trigger

USINT

0x82 — Server, Transport Class 2

(If alloc_choice != polled and ack suppression is enabled

then value = 0x80)

4

Get

Produced Connection ID

UINT

01111xxxxxx

xxxxxx=node

address

5

Get

Consumed Connection ID

UINT

10xxxxxx101

xxxxxx=node

address

6

Get

Initial Comm Characteristics

USINT

0x21

7

Get

Produced Connection Size

UINT

0 to 8

8

Get

Consumed Connection Size

UINT

0 to 8

9

Get/Set

Expected Packet Rate

UINT

in ms

12

Get/Set

Watchdog Action

USINT

0=transition to timed out

1=auto delete

2=auto reset

13

Get

Produced Connection Path Length

UINT

8

14

Get/Set

Produced Connection Path

21 04 00 25 (assy inst) 00 30 03

15

Get

Consumed Connection Path Length

UINT

8

16

Get/Set

Consumed Connection Path

21 04 00 25 (assy inst) 00 30 03