Rockwell Automation 284 ArmorStart User Manual User Manual

Page 139

Advertising
background image

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-17

➊ Not available on Bulletin 284A units. .

In Sink/Source
This parameter allows the installer to program the inputs to be sink or source.
0 = Sink
1 = Source

Parameter Number

32 ➊

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Pr FltState
This parameter in conjunction with Parameter 34 defines how Output A will respond
when a trip. When set to 1, Output A continue to operate as command via the
network. When set to 0, Output A will open or close as determined by setting in
Parameter 34.

Parameter Number

33

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Pr FltValue
This parameter determines the state the Out A assumes when a trip occurs and
Parameter 33 is set to 0.
0 = Open
1 = Close

Parameter Number

34

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA DN FltState
This parameter in conjunction with Parameter 36 defines how Output A will respond
when a DeviceNet network fault occurs. When set to 1, Output A will hold state prior
to trip occurrence. When set to 0, Output A will open or close as determined by
setting in Parameter 36.

Parameter Number

35

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA DN FltValue
This parameter determines the state that Output A assumes when a DeviceNet
network fault occurs and Parameter 35 is set to 0.
0 = Open
1 = Close

Parameter Number

36

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0