Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-37

Accel Time 1
Sets the rate of acceleration for all speed increases.

Parameter Number

139

Related Parameters

138, 140, 151, 152, 167,

170…173

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

0.1 sec

Minimum Value

0.0 sec

Maximum Value

600.0 sec

Default Value

10.0 sec

Decel Time 1
Sets the rate of deceleration for all speed decreases.

Parameter Number

140

Related Parameters

138, 139, 151, 152, 168,

170…173

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

0.1 sec

Minimum Value

0.1 sec

Maximum Value

600.0 sec

Default Value

10.0 sec

Reset To Defaults

Resets all parameter values to factory defaults.
0 = Ready/Idle (Default)
1 = Factory Rset

Parameter Number

141

Access Rule

GET/SET

Data Type

BOOL

Group

Basic Program Group

Units

Minimum Value

1

Maximum Value

1

Default Value

0

Maximum Freq

Accel Time

--------------------------------------

Accel Rate

=

Maximum Freq

Decel Time

--------------------------------------

Decel Rate

=

Stop drive before changing this parameter.

Motor OL Ret
Enables/disables the Motor overload Retention function. When Enabled, the value
held in the motor overload counter is saved at power-down and restored at power-
up. A change to this parameter setting resets the counter.
0 = Disabled (Default)
1 = Enabled

Parameter Number

143

Access Rule

GET/SET

Data Type

BOOL

Group

Basic Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0