Rockwell Automation 284 ArmorStart User Manual User Manual

Page 141

Advertising
background image

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-19

OutB DN FltValue
This parameter determines the state that Output B assumes when a DeviceNet
network fault occurs and Parameter 41 is set to 0.
0 = Open
1 = Close

Parameter Number

42

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutB DN IdlState
This parameter in conjunction with Parameter 44 defines how Output B will respond
when the DeviceNet network is idle. When set to 0, Output B will open or close as
determined by the setting in Parameter 44.
The DN Flt parameters supersede the Dn Idl parameters.

Parameter Number

43

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutB DN IdlValue
This parameter determines the state that Output B assumes when the network is
idle and Parameter 43 is set to 0.
0 = Open
1 = Close

Parameter Number

44

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Advertising
This manual is related to the following products: