Bulletin 280/281 Programmable Parameters

3-19

Zone Produced EPR

The Expected Packet Rate in
msec. Defines the rate at which
ZIP data is produced. Defaults to
75 msec.

Parameter Number

68

Access Rule

GET/SET

Data Type

UINT

Group

Zip Parameter

Units

msec

MinimumValue

0

Maximum Value

65535

Default Value

75

Zone Produced PIT

The Production Inhibit Time in
msec. Defines the minimum time
between Change of State data
production

Parameter Number

69

Access Rule

GET/SET

Data Type

UINT

Group

ZIP Parameters

Units

msec

MinimumValue

0

Maximum Value

65535

Default Value

75

Zone #1 MAC ID

The node address of the device
whose data is to be consumed
for zone 1

Parameter Number

70

Access Rule

GET/SET

Data Type

USINT

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

64

Default Value

64

Zone #2 MAC ID

The node address of the device
whose data is to be consumed
for zone 2

Parameter Number

71

Access Rule

GET/SET

Data Type

USINT

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

64

Default Value

64

Zone #3 MAC ID

The node address of the device
whose data is to be consumed
for zone 3

Parameter Number

72

Access Rule

GET/SET

Data Type

USINT

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

64

Default Value

64