Bulletin 283 CIP Information
C-7
Table C.12 Instance 181 — This is a “Read Only” Status Assembly
➊
➊
Note: This assembly does not exist on the Bulletin 283A.
Table C.13 Instance 182 — This is a “Read/Write” Control Assembly
Table C.14 Instance 183 This is a “Read Only” Status Assembly
Table C.15 Instance 184 This is a “Read Only” Status Assembly
➋
If Bulletin 283A is selected.
Table C.16 Instance 185 This is a “Read Only” Status Assembly
➌Refers to source brake contactor status.
Instance 181 — Hardware Inputs 1…16
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
—
—
—
—
Input 3
Input 2
Input 1
Input 0
1
Reserved
Instance 182 — Consumed Network Inputs 1…16
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Net Input
8
Net Input
7
Net Input
6
Net Input
5
Net Input
4
Net Input
3
Net Input
2
Net Input
1
1
Net Input
16
Net Input
15
Net Input
14
Net Input
13
Net Input
12
Net Input
11
Net Input
10
Net Input
9
Instance 183 — Produced Network Outputs 1…15
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Net Out 8 Net Out 7 Net Out 6 Net Out 5 Net Out 4 Net Out 3 Net Out 8 Net Out 1
1
Reserved
Net Out
15
Net Out
14
Net Out
13
Net Out
12
Net Out
11
Net Out
10
Net Out 9
Instance 184 — Trip Status
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
OverTemp
I/O Fault
Control
Power
Phase
Rotation
SCR
Short
Phase
Loss
OL Trip
Short
Circuit
1
Misc.
Fault
Reserved
Hw Fault EEPROM
Heatsink
Temp
Internal
Comm
DNet
Power
Loss
Phase
Imbalance
Reserved
➋
Instance 185 — Starter Status
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At Ref
Net Ref
Status
Net Ctl
Status
Ready
—
Running
Fwd
Warning
Tripped
1
Contact
2 ➌
—
140M On
HOA
Status
Keypad
Hand
Bypass
Stopping Starting