Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-51

Figure 6.7

Current Limit 2
Maximum output current allowed before current limiting occurs. This parameter is
only active if Parameters 151, 152, 153, and 154 (Digital Inx Sel) is set to 25
Current Lmt2 and is active.

Parameter Number

218

Related Parameters

133, 151, 152, 153, 154, 189

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 A

Minimum Value

0.1 A

Maximum Value

Drive rated amps x 1.8

Default Value

Drive rated amps x 1.5

Skip Frequency
Sets the frequency at which the drive will not operate.

Parameter Number

219

Related Parameters

220

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 hz

Minimum Value

0.0

Maximum Value

400.0 Hz

Default Value

0.0 Hz

Skip Frq Band
Determines the brand width around Parameter 219 (Skip Frequency). Parameter
220 (Skip Frquency) is split applying 1/2 above and 1/2 below the actual skip
frequency. A setting of 0.0 disables this parameter.

Parameter Number

220

Related Parameters

219

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 Hz

Minimum Value

0.0 Hz

Maximum Value

30.0 Hz

Default Value

0.0 Hz