Rockwell Automation 284 ArmorStart User Manual User Manual

Page 98

Advertising
background image

4-8

Bulletin 283 Programmable Parameters

Starter Command

The parameter provides the
status of the starter command.

Parameter Number

7

Access Rule

GET

Data Type

WORD

Group

DeviceLogix

Units

Minimum Value

0

Maximum Value

255

Default Value

0

Bit

Function:

7

6

5

4

3

2

1

0

X

Run Fwd

X

Reserved

X

Fault Reset

X

Reserved

X

Reserved

X

Reserved

X

User Out A

X

User OUt B

Network Override

This parameter allows for the
local logic to override a Network
fault
0 = Disable
1 = Enable

Parameter Number

8

Access Rule

GET/SET

Data Type

BOOL

Group

DeviceLogix

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Comm Override

This parameter allows for local
logic to override the absence of
an I/O connection
0 = Disable
1 = Enable

Parameter Number

9

Access Rule

GET/SET

Data Type

BOOL

Group

DeviceLogix

Units

Minimum Value

0

Maximum Value

1

Default Value

0