6-30

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

Advanced Program Group

Decel Time 1
Sets the rate of deceleration for all speed decreases.

Parameter Number

140

Related Parameters

138, 139, 151, 152, 153, 154,

168, 170…173, 174…177,

and 240…247

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program

Units

0.1 sec

Minimum Value

0.1 sec

Maximum Value

600.0 sec

Default Value

10.0 sec

Reset To Defaults

Resets all parameter values to factory defaults.
0 = Ready/Idle (Default)
1 = Factory Rset

Parameter Number

141

Access Rule

GET/SET

Data Type

BOOL

Group

Basic Program Group

Units

Minimum Value

1

Maximum Value

1

Default Value

0

Motor OL Ret

Enables/disables the Motor overload Retention function. When Enabled, the value
held in the motor overload counter is saved at power-down and restored at power-
up. A change to this parameter setting resets the counter.
0 = Disabled (Default)
1 = Enabled

Parameter Number

143

Access Rule

GET/SET

Data Type

BOOL

Group

Basic Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Maximum Freq

Decel Time

--------------------------------------

Decel Rate

=

Stop drive before changing this parameter.

151 (Digital In 1 SEL)
152 (Digital In 2 SEL)
153 (Digital In 3 SEL)
154 (Digital In 4 SEL)

Selects the function for the digital inputs.

Parameter Number

151, 152, 153, 154

Related Parameters

112, 114, 138…140, 167,

168, 170…173, 174…177,

178, 179, 240…247

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

See Table 6.2 for details

Minimum Value

Maximum Value

Default Value

Stop drive before changing this parameter.