Rockwell Automation 284 ArmorStart User Manual User Manual

Page 170

Advertising
background image

5-48

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

Reverse Disable

Enables/disables the function that allows the direction of the motor rotation to be
changed. The reverse command may come from a digital command or serial
command. All reverse inputs including two-wire Run Reverse will be ignored with
reverse disabled.
0 = Disabled
1 = Enabled

Parameter Number

195

Related Parameters

106

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Flying Start En
Sets the condition that allows the drive to reconnect to a spinning motor at actual
RPM.
0 = Disabled
1 = Enabled

Parameter Number

196

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Compensation
Enables/disables correction options that may improve problems with motor
instability
0 = Disabled
1 = Electrical (Default)
Some drive/motor combinations have inherent instabilities which are exhibited as
non-sinusoidal motor currents. This setting attempts to correct this condition
2 = Mechanical
Some motor/load combinations have mechanical resonances which can be excited
by the drive current regulator. This setting slows down the current regulator
response and attempts to correct this condition.
3 = Both

Parameter Number

197

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

3

Default Value

1

SW Current Trip
Enables/disables a software instantaneous (within 100 ms) current trip.

Parameter Number

198

Related Parameters

133

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 A

Minimum Value

0.0

Maximum Value

Drive rated amps x 2

Default Value

0.0 (Disabled)

Process Factor
Scales the output frequency value displayed by Parameter 110 (Process Display).
Output Freq x Process Factor = Process Display

Parameter Number

199

Related Parameters

110

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1

Minimum Value

0.1

Maximum Value

999.9

Default Value

30.0

Stop drive before changing this parameter.

Advertising
This manual is related to the following products: