Bulletin 283 CIP Information

Table C.26 Instance 163 is the standard input (produced) assembly with

Network Outputs

For Bulletin 283A only.

SMC Dialog Plus Native
Assemblies

These assembly instances have the same data format as the ScanPort
control and status registers on the SMC Dialog Plus soft starter. They
are intended for use by customers that are accustomed to using the
SMC Dialog Plus product on DeviceNet.

Table C.27 SMC Dialog Plus Native Consumed Assembly

Table C.28 SMC Dialog Plus Native Produced Assembly

Instance 163 — Standard Produced Starter with Network Outputs

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Ready

Running

Fwd

Tripped

1

140M On

HOA

Stat.

User In 4 User In 3 User In 2 User In 1

Reserved

Reserved

Reserved

Reserved

2

Net Out 8 Net Out 7 Net Out 6 Net Out 5 Net Out 4 Net Out 3 Net Out 2 Net Out 1

3

Logic

Enable

Stat

Net Out

15

Net Out

14

Net Out

13

Net Out

12

Net Out

11

Net Out

10

Net Out 9

4

ZIP CCV (low)

5

ZIP CCV (high)

Instance 172 — SMC Dialog Plus Native Consumed Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserved

Reserved

FLT

Reset

Reserved

Start

Stop

1

Reserved

Instance 172 — SMC Dialog Plus Native Produced Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Faulted Reserved Stopping Starting

Reserved

Running

Enabled

1

In 4 Stat In 3 Stat In 2 Stat In 1 Stat

Reserved

At Speed