Rockwell Automation 284 ArmorStart User Manual User Manual

Page 404

Advertising
background image

D-4

Bulletin 284 CIP Information

DeviceNet Object — CLASS CODE 0x0003

The following class attributes are supported for the DeviceNet Object:

Table D.6

DeviceNet Object Class Attributes

A single instance (Instance 1) of the DeviceNet Object will be
supported. The following instance attributes are supported:

Table D.7

DeviceNet Object Instance Attributes

1M baud is only available on the Bulletin 284A.

See Table D.8

Table D.8

Allocation_byte

The following services are implemented for the DeviceNet Object:

Table D.9

DeviceNet Object Common Services

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

2

Attribute

ID

Access

Rule

Name

Data Type

Value

1

Get/Set

Node Address

USINT

0…63

2

Get/Set

Baud Rate

USINT

0 = 125K
1 = 250K
2 = 500K
3 = 1M ➊

5

Get

Allocation Info

• Allocation Choice
• Master Node Addr

Structure of:

• BYTE
• USINT

Allocation_byte ➋
0…63 = address
255 = unallocated

8

Get

MAC ID Switch Value

BOOL

0…63

Bit 0

Explicit messaging

Bit 1

Polled I/O

Bit 4

COS I/O

Bit 5

Cyclic I/O

Bit 6

Acknowledge Suppression

Service

Code

Implemented for

Service

Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x4B

No

Yes

Allocate_Master/Slave _Connection_Set

0x4C

No

Yes

Release_Master/Slave _Connection_Set

Advertising