Bulletin 280/281 Programmable Parameters

3-15

OutA Pr FltValue

This parameter determines the
state the Out A assumes when a
trip occurs and Parameter 33 is
set to “0”
0 = Open
1 = Close

Parameter Number

34

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA DN FltState
This parameter in conjunction
with Parameter 36 defines how
Output A will respond when a
DeviceNet network fault occurs.
When set to “1”, Output A will
hold state prior to trip
occurrence. When set to “0”,
Output A will open or close as
determined by setting in
Parameter 36

Parameter Number

35

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA DN FltValue

This parameter determines the
state that Output A assumes
when a DeviceNet network fault
occurs and Parameter 35 is set to
“0”
0 = Open
1 = Close

Parameter Number

36

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA DN IdlState
This parameter in conjunction
with Parameter 38 defines how
Output A will respond when the
DeviceNet network is idle. When
set to “0”, Output A will open or
close as determined by the
setting in Parameter 38 The
DN Flt parameters supersede the
Dn Idl parameters

Parameter Number

37

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA DN IdlValue

This parameter determines the
state that Output A assumes
when the network is idle and
Parameter 37 is set to “0”
0 = Open
1 = Close

Parameter Number

38

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0