2-24

Installation and Wiring

Wiring

Power, Control, Safety Monitor Inputs, and Ground Wiring

Table 2.1 provides the power, control, and ground wire capacity and
the tightening torque requirements. The power, control, ground, and
safety monitor terminals will accept a maximum of two wires per
terminal.

Table 2.1

Power, Control, Safety Monitor Inputs, Ground Wire Size, and

Torque Specifications

Terminals

Wire Size

Torque

Wire Strip Length

Power

and

Ground

Primary/Secondary

Terminal:

1.5…4.0 mm

2

(#16 …#10 AWG)

Primary Terminal:

10.8 lb.-in.

(1.2 N•m)

Secondary Terminal:

4.5 lb.-in

(0.5 N•m)

0.35 in. (9 mm)

Control and Safety

Monitor Inputs

1.0 mm

2

…4.0 mm

2

(#18…#10 AWG)

6.2 lb.-in

(0.7 N•m)

0.35 in. (9 mm)