Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

Maximum Freq

Sets the Highest frequency the drive will output continuously.

Parameter Number

135

Related Parameters

101, 102, 113, 134, 178, 211,

213, 215

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

240

Default Value

60.0

Start Source

Sets the control scheme used to start the Bulletin 284 ArmorStart.
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port

Parameter Number

136

Related Parameters

112 and 137

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

Minimum Value

0

Maximum Value

5

Default Value

5

Stop Mode
Valid Stop Mode for the Bulletin 284 ArmorStart are the following:
0 = Ramp, CF Ramp to Stop. Stop command clears active fault.
1 = Coast, CF Coast to Stop. Stop command clears active fault.
2 = DC Brake,CF DC Injection Braking Stop. Stop command clears active fault.
3 = DCBrkAuto, CF DC injection Braking with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time)
or
Drive shuts off if the drive detects that the motor is stopped. Stop command clears
active fault
4 = Ramp Ramp to Stop
5 = Coast Coast to Stop
6 = DC Brake DC Injection Braking Stop
7 = DC BrakeAuto DC Injection Stop with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time)
or
Drive shuts off if current limit is exceeded

Parameter Number

137

Related Parameters

136, 180, 182, 205

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

Minimum Value

0

Maximum Value

7

Default Value

0

Speed Reference
Valid Speed References for the Bulletin 284 ArmorStart are the following:
1 = Internal Freq
4 = Preset Freq
5 = Comm port

Parameter Number

138

Related Parameters

101, 102, 112, 139, 140, 151,

152, 169, 170…173, 210,

211, 213, 232

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program Setup

Units

Minimum Value

0

Maximum Value

5

Default Value

5

Stop drive before changing this parameter.

Stop drive before changing this parameter.