Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-9

DeviceNet Group

Autobaud Enable
When this parameter is enabled, the device will attempt to determine the network
baud rate and set its baud rate to the same, provided network traffic exists. At least
one node with an established baud rate must exist on the network for autobaud to
occur.
0 = Disable
1 = Enable

Parameter Number

10

Access Rule

GET/SET

Data Type

BOOL

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

1

Default Value

1

Consumed I/O Assy
This parameter selects the format of the I/O data consumed

Parameter Number

11

Access Rule

GET/SET

Data Type

USINT

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

188

Default Value

164

Produced I/O Assy
This parameter selects the format of the I/O data produced.

Parameter Number

12

Access Rule

GET/SET

Data Type

USINT

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

190

Default Value

165

Prod Assy Word 0
This parameter is used to build bytes 0-1 for produced assembly 120.

Parameter Number

13

Access Rule

GET/SET

Data Type

INT

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

216

Default Value

1

Produced Assy Word 1
This parameter is used to build bytes 2-3 for produced assembly 120

Parameter Number

14

Access Rule

GET/SET

Data Type

INT

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

216

Default Value

4