Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-39

155 (Relay Out Sel)
Sets the condition that changes the state of the output relay contacts.

See Table 5.C for details

Parameter Number

155

Related Parameters

133, 156, 192

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

21

Default Value

6

Table 5.C Relay Out Sel Options

Options

Description

0

Ready/Fault

(Default)

Relay changes state when power is applied. This indicates the drive is ready for operation. Relay returns drive to
shelf state when power is removed or a fault occurs.

1

At Frequency

Drive reached commanded frequency.

2

MotorRunning

Motor is receiving power from drive.

3

Reverse

Drive is commanded to run in reverse direction.

4

Motor Overld

Motor overload condition exists.

5

Ramp Reg

Ramp regulator is modifying the programmed accel/decal times to avoid overcurrent or overvoltage fault from
occurring.

6

Above Freq

Drive exceeds the frequency (Hz) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set
threshold.

7

Above Cur

Drive exceeds the current (% Amps) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set
threshold.

8

Above DCVolt

Drive exceeds the DC bus voltage value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set
threshold.

9

Retries Exst

Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.

10

Above Anlg V

Option not valid for Bulletin 284 ArmorStart.

11…19

Not Used

Reserved

20

ParamControl

Enables the output to be controlled over the network communications by writing to Parameter 156 (Relay Out
Level) (0 = Off, 1 = ON).

21

NonRec Fault

Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.

Relay Out Level
Sets the trip point for the digital output relay if the value of Parameter 155 (Relay
Out Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.

Parameter Number

156

Related Parameters

155

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1

Minimum Value

0.0

Maximum Value

9999

Default Value

2.0

Parameter 155 Setting

Parameter 156 Min./Max.

6

0/400 Hz

7

0/180%

8

0/815V

10

0/100%

20

0/1