Rockwell Automation 284 ArmorStart User Manual User Manual

Page 357

Advertising
background image

Bulletin 280/281 CIP Information

B-13

Instances 5 through 7 are available group 3 explicit message
connections that are allocated through the UCMM. The following
attributes are supported:

Table B.31 Connection Object Instance 5-7 Attributes

Instances 8-11 are ZIP Consumers. The following instance attributes
will be supported:

Table B.32 Connection Object Instances 8-11 Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0=nonexistant

1=configuring
3=established

4=timed out

2

Get

Instance Type

USINT

0=Explicit

Message

3

Get

Transport Class Trigger

USINT

0x83 — Server, Transport Class 3

4

Get

Produced Connection ID

UINT

Depends on message group and Message ID

5

Get

Consumed Connection ID

UINT

Depends on message group and Message ID

6

Get

Initial Comm Characteristics

USINT

0x33 (Group 3)

7

Get

Produced Connection Size

UINT

0

8

Get

Consumed Connection Size

UINT

0XFFFF

9

Get/Set

Expected Packet Rate

UINT

in ms

12

Get

Watchdog Action

USINT

01 = auto delete

03 = deferred delete

13

Get

Produced Connection Path Length

UINT

0

14

Get

Produced Connection Path

Empty

15

Get

Consumed Connection Path Length

UINT

0

16

Get

Consumed Connection Path

Empty

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0=nonexistant

1=configuring
3=established

2

Get

Instance Type

USINT

1=I/O Connection

3

Get

Transport Class Trigger

USINT

0x20 (COS, unacknowledged)

4

Get

Produced Connection ID

UINT

FFFF (not producing data)

5

Get

Consumed Connection ID

UINT

01101xxxxxx

xxxxxx=node address

6

Get

Initial Comm Characteristics

USINT

0xF0 (unacknowledged)

7

Get

Produced Connection Size

UINT

0

8

Get

Consumed Connection Size

UINT

8

9

Get/Set

Expected Packet Rate

UINT

in milliseconds

12

Get

Watchdog Action

USINT

2=auto reset

13

Get

Produced Connection Path Length

UINT

0

14

Get

Produced Connection Path

0

15

Get

Consumed Connection Path Length

UINT

8

16

Get

Consumed Connection Path

21 0E 03 25 01 00 30 02

Advertising