Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-15

User I/O Group

➊Not available with the Bulletin 284A.

Off-to-On Delay

This parameter allows the installer to program a time duration before being reported
ON.

Parameter Number

30

Access Rule

GET/SET

Data Type

UINT

Group

User I/O

Units

ms

Minimum Value

0

Maximum Value

65.000

Default Value

0

On-to-Off Delay

This parameter allows the installer to program a time duration before being reported
OFF.

Parameter Number

31

Access Rule

GET/SET

Data Type

UINT

Group

User I/O

Units

ms

Minimum Value

0

Maximum Value

65.000

Default Value

0

In Sink/Source

This parameter allows the installer to program the inputs to be sink or source.
0 = Sink
1 = Source

Parameter Number

32

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Pr FltState
This parameter in conjunction with Parameter 34 defines how Output A will respond
when a trip. When set to 1, Output A continue to operate as command via the
network. When set to 0, Output A will open or close as determined by setting in
Parameter 34.

Parameter Number

33

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Pr FltValue
This parameter determines the state the Out A assumes when a trip occurs and
Parameter 33 is set to 0.
0 = Open
1 = Close

Parameter Number

34

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0