DeviceNet™ Commissioning

8-9

Setting the Motor FLA(Bulletin 283)

The product should now be configured and communicating on the
network. The last step is to program the proper motor FLA setting
(parameter #106). This can be accomplished by using software such
as RSNetWorx for DeviceNet or a handheld DeviceNet tool.

Use the software to access the device parameters screen. By default
the motor FLA is set to the minimum FLA setting for the device and
the overload trip class is set to 10. Set these parameters to the desired
values and download to the device.

Select FLA setting (parameter #106) and enter a value that
corresponds to the FLA of the motor connected to the ArmorStart.
Make sure the Single radio button is selected and then select
Download to Device.

The Overload Trip class for the Bulletin 283 Distributed Motor
Controller is class 10.

The proper motor protection is now in place.

Figure 8.3 RSNetWorx Parameter Screen