Bulletin 284 CIP Information

D-3

Identity Object

A single instance of the Identity Object is supported. The following
instance attributes are supported:

Table D.4

Identity Object Instance Attributes

The following common services are implemented for the Identity
Object:

Table D.5

Identity Object Common Services

Message Router — CLASS CODE 0x0002

No class or instance attributes are supported. The message router
object exists only to rout explicit messages to other objects.

Attribute

ID

Access

Rule

Name

Data Type

Value

1

Get

Vendor

UINT

1

2

Get

Device Type

UINT

22 or 133

3

Get

Product Code

UINT

See Table D.1

4

Get

Revision

Major Revision
Minor Revision

Structure of:

USINT
USINT

Indicates Software Firmware
Revision Number

5

Get

Status

WORD

Bit 0: 0 = not owned; 1 =
owned by master
Bit 2: 0 = Factory Defaulted;
1 = Configured
Bit 8: Minor Recoverable fault
Bit 9: Minor Unrecoverable fault
Bit 10: Major Recoverable fault
Bit 11: Major Unrecoverable
fault

6

Get

Serial Number

UDINT

Unique Number for Each Device

7

Get

Product Name

String Length

ASCII String

Structure of:

USINT

STRING

Product code specific
See Table D.1.

8

Get

State

USINT

Returns the value
3 = Operational

9

Get

Configuration

Consistency

Value

UINT

Unique value depending on
output of the parameter
checksum algorithm.

10

Get/Set

Heartbeat Interval

USINT

In seconds. Default = 0

Service
Code

Implemented for

Service
Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x05

No

Yes

Reset

0x10

No

Yes

Set_Attribute_Single