Rockwell Automation 284 ArmorStart User Manual User Manual

Page 226

Advertising
background image

6-52

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

Table 6.7

Stall Fault Time
Sets for the fault time that the drive will remain in stall mode before a fault is issued.
0 = 60 sec (Default)
1 = 120 sec
2 = 240 sec
3 = 360 sec
4 = 480 sec
5 = Flt Disabled

Parameter Number

221

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

5

Default Value

0

Analog In Loss
Selects drive action when an input signal loss is detected. Signal loss is defined as
an analog signal less than 1V. The signal loss event ends and normal operation
resumes when the input signal level is greater than or equal to 1.5V. If using a
0…10V analog input, set parameter 210 (Anlg In 0…10V Lo) to a minimum of 20%
(i.e., 2 volts).

Parameter Number

222

Related Parameters

210, 211, 232

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

See Table 6.7 for details

Minimum Value

Maximum Value

Default Value

Options

Description

0

Disabled (Default)

1

Fault (F29)

F29 Analog Input Loss

2

Stop

Uses P037 (Stop Mode)

3

Zero Ref

Drive runs at zero speed reference

4

Min Freq Ref

Drive runs at minimum frequency

5

Max Freq Ref

Drive runs at maximum frequency

6

Int Freq Ref

Drive runs at internal frequency

10V Bipolar Enbl
Enables/disables bipolar control. In bipolar mode, direction is commanded by the
sign of the reference.
Options
0 = Unipolar In (Default) 0…10V only
1 = Bipolar In +/- 10V

Parameter Number

223

Related Parameters

138, 211

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0