Chapter

5

Bulletin 284 Programmable Parameters
for Volts per Hertz Controllers

This chapter describes each programmable parameter and its function
for Bulletin 284 Volts per Hertz Controllers.

Parameter Programming

Each Distributed Motor Controller type will have a common set of
parameters followed by a set of parameters that pertain to the
individual starter type.

Refer to Chapter 8, DeviceNet™ Commissioning, for instructions in
using RSNetWorx

for DeviceNet

to modify parameter settings.

Refer to Chapter 11, ArmorStart® to ArmorPoint® Connectivity, for
instructions to modify parameter settings when using the Bulletin
284A with the ArmorPoint® distributed I/O products.

Important: Resetting the Factory Default Values Parameter 47, Set

to Defaults, allows the installer to reset all parameter to
the factory default values. It also resets the MAC ID to its
factory default after DeviceNet Power is cycled if
switches are set >63.

Important: Parameter setting changes downloaded to the

ArmorStart® take effect immediately, even during a
running status.

Important: Parameter setting changes made in a configuration tool

such as RSNetworx for DeviceNet do not take effect in
the ArmorStart until the installer applies or downloads
the new settings to the device.

Parameter Group Listing

The Bulletin 284D ArmorStart contains ten parameter groups. The
parameters shown in the DeviceLogix™ Setup, DeviceNet Setup,
Starter Protection Setup, User I/O Setup, Misc. Parameter Setup,
Drive DeviceNet, ZIP Parameters, Display Group, Basic Program,
and Advanced Program are discussed in this chapter.