5-42

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

DC Brake Level
Defines the maximum DC brake current, in amps, applied to the motor when
Parameter 137 (Stop Mode) is set to either Ramp or DC Brake.

Parameter Number

181

Related Parameters

137, 180

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 A

Minimum Value

0.0

Maximum Value

Drive rated amps X 1.8

Default Value

Drive rated amps X 0.05

ATTENTION

!

If a hazard of injury due to movement of equipment or material exists, an
auxiliary mechanical braking device must be used.

This feature should not be used with synchronous or permanent magnet
motors. Motors may be demagnetized during braking.

DB Resistor Sel

Enables/disables external dynamic braking.

Parameter Number

182

Related Parameters

137

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1

Minimum Value

0

Maximum Value

99

Default Value

0

Stop drive before changing this parameter.

Setting

Min./Max.

0

Disabled

1

Normal RA Res (5% Duty Cycle)

2

No Protection (100% Duty Cycle)

3…99

x% Duty Cycle Limited (3…99% of Duty Cycle)