5-14

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

Pr Fault Reset
This parameter resets the Protection Fault on a transition 0 > 1.

Parameter Number

25

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

StrtrDN FltState
This parameter in conjunction with Parameter 27 defines how the starter will
respond when a DeviceNet fault occurs. When set to 1, hold to last state occurs.
When set to 0, will go to DnFlt Value on DN faults as determined by Parameter 27.

Parameter Number

26

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

StrtrDN FltValue
This parameter determines if the starter will be commanded in the event of a
DevceNet fault and Parameter 26 is set to 0.
0 = OFF
1 = ON

Parameter Number

27

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

StrtrDN IdlState
This parameter in conjunction with Parameter 29 defines how the starter will respond
when a DeviceNet network is idle. When set to 1, hold to last state occurs. When set
to 0, will go to DnFlt Value on DN faults as determined by Parameter 29.
0 = Go to Idle Value
1 = Hold Last State

Parameter Number

28

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

StrtrDN IdlValue
This parameter determines the state that starter assumes when the network is idle
and Parameter 28 is set to 0.
0 = OFF
1 = ON

Parameter Number

29

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0