Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-29

Stop Mode
Valid Stop Mode for the Bulletin 284 ArmorStart are the following:
0 = Ramp, CF Ramp to Stop. Stop command clears active fault.
1 = Coast, CF Coast to Stop. Stop command clears active fault.
2 = DC Brake,CF DC Injection Braking Stop. Stop command clears active fault.
3 = DCBrkAuto, CF DC injection Braking with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time) or
Drive shuts off if the drive detects that the motor is stopped. Stop command clears
active fault
4 = Ramp Ramp to Stop
5 = Coast Coast to Stop
6 = DC Brake DC Injection Braking Stop
7 = DC BrakeAuto DC Injection Stop with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time)
or
Drive shuts off if current limit is exceeded
8 = Ramp + EM B, CF Ramp to Stop with EM Brake Control. Stop command clears
active fault.
9 = Ramp + EM Brk Ramp to Stop with EM Brake Control.

Parameter Number

137

Related Parameters

136, 180, 181, 182, 205, 260,

261

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program

Units

Minimum Value

0

Maximum Value

9

Default Value

9

Speed Reference
Valid Speed References for the Bulletin 284 ArmorStart are the following:
1 = Internal Freq
2 = 0…10V Input
4 = Preset Freq
5 = Comm port
6 = Stp Logic
9 = Jog Freq

Note: Option 2 must be selected when using 0…10V Analog Input.

Parameter Number

138

Related Parameters

101, 102, 112, 139, 140, 151,

152, 153, 154, 169,

170…173, 174…177, 210,

211, 213, 232, 240…247,

and 250…257

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program

Units

Minimum Value

0

Maximum Value

7

Default Value

5

Accel Time 1
Sets the rate of acceleration for all speed increases.

Parameter Number

139

Related Parameters

138, 140, 151, 152, 153, 154,

167, 170…173, 174…177,

and 240…247

Access Rule

GET/SET

Data Type

UINT

Group

Basic Program

Units

0.1 sec

Minimum Value

0.0 sec

Maximum Value

600.0 sec

Default Value

10.0 sec

Maximum Freq

Accel Time

--------------------------------------

Accel Rate

=