Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-53

Var PWM Disable

Enables/disables a feature that varies the carrier frequency for the PWM output
waveform defined by Parameter 191 (PWM Frequency).
0 = Enabled
1 = Disabled
Disabling this feature when low frequency condition exists may result in IGBT stress
and nuisance tripping.

Parameter Number

224

Related Parameters

191

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Torque Perf Mode

Enables/disables sensorless vector control operation.
0 = V/Hz
1 = Sensrls Vect

Parameter Number

225

Related Parameters

184, 185, 186, 187, 227

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

1

Motor NP FLA
Set to the motor nameplate full load amps.

Parameter Number

226

Related Parameters

227

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 A

Minimum Value

0.1

Maximum Value

Drive rated amps x 2

Default Value

Drive rated amps

Stop drive before changing this parameter.

Stop drive before changing this parameter.