Bulletin 280/281 Programmable Parameters

3-11

Not available on the Bulletin 280A/281A.

PrFlt Reset Mode

This parameter configures the
Protection Fault reset mode.

0= Manual
1= Automatic

Parameter Number

23

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Pr Fault Enable

This parameter enables the
Protection Fault by setting the bit
to 1

Parameter Number

24

Access Rule

GET/SET

Data Type

WORD

Group

Starter Protection Setup

Units

Minimum Value

0

Maximum Value

16383

Default Value

12419

Bit

Function

13 12 11 10

9

8

7

6

5

4

3

2

1

0

— — — — — — — — — — — — —

X

Short Circuit

— — — — — — — — — — — —

X

Overload

— — — — — — — — — — —

X

— —

Phase Loss

— — — — — — — — — —

X

— — —

Reserved

— — — — — — — — —

X

— — — —

Reserved

— — — — — — — —

X

— — — — —

Control Power

— — — — — — —

X

— — — — — —

I/O Fault

— — — — — —

X

— — — — — — —

Over Temperature

— — — — —

X

— — — — — — — —

Phase Imbalance

— — — —

X

— — — — — — — — —

Dnet Power Loss

— — —

X

— — — — — — — — — —

Reserved

— —

X

— — — — — — — — — — —

Reserved

X

— — — — — — — — — — — —

Eeprom

X

— — — — — — — — — — — — —

HW Fault

Pr Fault Reset

This parameter resets the
Protection Fault on a transition of
0-->1.

Parameter Number

25

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0