Group Motor Installations

E-7

Table E.1

Extended NFPA 79, Table 7.210.4, Relationship Between

Conductor Size and Maximum Rating or Setting of Short-Circuit
Protective Devices for Power Circuits

➊ For 16 AWG conductors the branch circuit breaker must be marked for use the 16 AWG wire, NFPA

79, 12.6.1.1.

➋ The UL Certificate of Compliance for the ArmorStart Distributed Motor Controllers models 280*-*10*,

281*-*10*, 283*-*10*, 284*-*10*; and ArmorConnect input cable media 280*-M22*-M*, 280S-
PWRM22*-M* cable assembly branch circuit taps, and 280*-M22*-M1 ArmorConnect panel mounting
fittings allows 16 AWG conductors to be used when part of ArmorStart and ArmorConnect components.

➌ The 280*-PWRM22*-M* ArmorConnect cable assembly taps and 280*-22*-M1 panel mounted fittings

with 16 AWG conductors are suitably protected when protected in the branch circuit by a 40A non-
time delay fuse.

➍ The 280*-PWRM22*-M* ArmorConnect Cable Assembly taps and 280*-22*-M1 Panel Mounted Fittings

with 16 AWG conductors are suitably protected when protected in the branch circuit by a 20A time
delay fuse.

The Listed ArmorStart motor controllers with their factory supplied
motor cable carries the marked maximum ratings shown in the
following table.

➊ Class J, CC, and T fuses only.

➋ ArmorConnect power media and tees may only be used with fuses.

Max. Ratings

Conductor Size

(AWG)

Non-Time Delay Fuse or

Inverse Time Circuit

Breaker

(amperes)

Time Delay or Dual Element

Fuse (amperes)

16

40

20

14

60

30

12

80

40

10

100

50

8

150

80

6

200

100

4

250

125

Max. Ratings

Voltage

480Y/277

480

600Y/347

600

Sym. Amps RMS

65 kA

65 kA

30 kA

30 kA

Circuit Breaker

100 A

100 A

100 A

-

Fuse

100 A

100 A

100 A

60 A

ArmorConnect

60 A

60 A

60 A

60 A