Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-47

SW Current Trip
Enables/disables a software instantaneous (within 100 ms) current trip.

Parameter Number

198

Related Parameters

133

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 A

Minimum Value

0.0

Maximum Value

Drive rated amps x 2

Default Value

0.0 (Disabled)

Process Factor
Scales the output frequency value displayed by Parameter 110 (Process Display).
Output Freq x Process Factor = Process Display

Parameter Number

199

Related Parameters

110

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1

Minimum Value

0.1

Maximum Value

999.9

Default Value

30.0

Fault Clear

Resets a fault and clears the fault queue. Used primarily to clear a fault over
network communications.
0 = Ready/Idle (Default)
1 = Reset Fault
2 = Clear Buffer (Parameters 107…109 [Fault x Code])

Parameter Number

200

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

2

Default Value

0

Program Lock
Protects parameters against change by unauthorized personnel.
0 = Unlocked
1 = Locked

Parameter Number

201

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Testpoint Sel
Used by Rockwell Automation field service personnel.

Parameter Number

202

Related Parameters

119

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1 Hex

Minimum Value

0

Maximum Value

FFFF

Default Value

400

Stop drive before changing this parameter.