Bulletin 283 Programmable Parameters

4-31

Recommended maximum initial torque setting is 65%.

Recommended maximum soft stop time is 45 seconds.

Initial Torque

This parameter allows the
installer to select the initial
torque value to full voltage. The
initial torque value is adjustable
0…90% of locked rotor torque.

Parameter Number

112

Access Rule

GET/SET

Data Type

USINT

Group

Soft Start Setup

Units

% of LRT

Minimum Value

0

Maximum Value

90

Default Value

60

Soft Stop Time

The Soft Stop function can be
used with applications that
require an extended coast to rest.
When enabled, the voltage ramp
down time can be selected from
0…90 seconds. The motor will
stop when the motor voltage
drops to a point where the load
torque is greater than the motor
torque.

Parameter Number

113

Access Rule

GET/SET

Data Type

USINT

Group

Soft Start Setup

Units

Sec

Minimum Value

0

Maximum Value

90

Default Value

0

Kick Start

A kickstart, or boost, at the
beginning of the start mode is
intended to provide a current
pulse of 450% of full load
current. The kickstart time is
adjustable from
0.0…1.5 seconds. This allows
the motor to develop additional
torque at start for loads which
may need a boost to get you
started.

Parameter Number

114

Access Rule

GET/SET

Data Type

USINT

Group

Soft Start Setup

Units

0.0 Sec

Minimum Value

0.0

Maximum Value

1.5

Default Value

0.0

SCR Temp Reset Mode

The SMC-3 monitors the SCR
temperature by means of internal
thermistors. When the power
poles maximum rated
temperature is reached, the
microcomputer switches off the
SMC and a Heat Sink
Temperature fault is indicated via
LED.

0= Manual
1= Auto Reset

Parameter Number

115

Access Rule

GET/SET

Data Type

BOOL

Group

Soft Start Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

0