Rockwell Automation 284 ArmorStart User Manual User Manual

Page 212

Advertising
background image

6-38

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

.

➊ To activate 170 (Preset Freq 0) set 138 (Speed Reference) to option 4 Preset Freq.
➋ When a Digital Input is set to Accel 2 & Decel 2, and the input is active, that input overrides the

settings in this table.

170 (Preset Freq 0)
171 (Preset Freq 1)
172 (Preset Freq 2)
173 (Preset Freq 3)
174 (Preset Freq 4)
175 (Preset Freq 5)
176 (Preset Freq 6)
177 (Preset Freq 7)

Parameter Number

170…173, 174…177

Related Parameters

138, 139, 140, 151, 152, 152,
153, 167, 168, 240…247,
250…257

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

400.0

Default Value

See Table 6.A

Table 6.A 170…177 Preset Freq Options

Values
Provides a fixed frequency command value when 151…153 (Digital Inx Sel) is set to
4 Preset Frequencies.

170 Default ➊

0.0 Hz

171 Default

5.0 Hz

172 Default

10.0 Hz

173 Default

20.0 Hz

174 Default

30.0 Hz

175 Default

40.0 Hz

176 Default

50.0 Hz

177 Default

60.0 Hz

Min./Max.

0.0/400.0 Hz

Display

0.1 Hz

Input State of Digital In

1 (I/O Terminal 05 when

Parameter 151 = 4)

Input State of Digital In

2 (I/O Terminal 06 when

Parameter 152 = 4)

Input State of Digital In

3 (I/O Terminal 07 when

Parameter 153 = 4)

Frequency

Source

Accel/Decel

Parameter

Used

0

0

0

170 (Preset Freq 0)

(Accel Time 1)/(Decel Time 1)

1

0

0

171 (Preset Freq 1)

(Accel Time 1)/(Decel Time 1)

0

1

0

172 (Preset Freq 2)

(Accel Time 2)/(Decel Time 2)

1

1

0

173 (Preset Freq 3)

(Accel Time 2)/(Decel Time 2)

0

0

1

174 (Preset Freq 4)

(Accel Time 3)/(Decel Time 3)

1

0

1

175 (Preset Freq 5)

(Accel Time 3)/(Decel Time 3)

0

1

1

176 (Preset Freq 6)

(Accel Time 4)/(Decel Time 4)

1

1

1

177 (Preset Freq 7)

(Accel Time 4)/(Decel Time 4)

Jog Frequency
Sets the output frequency when the jog command is issued.

Parameter Number

178

Related Parameters

135, 151, 152, 153, 154, 179

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

400.0

Default Value

10.0

Advertising