9-2

Explicit Messaging on DeviceNet™

If a different I/O assembly is selected, the data size may change. It is
important to understand that the I/O assembly selected here will
directly affect the input and output mapping in the scanner’s scanlist
and the amount of Programmable Logic Controller (PLC) memory
reserved for this information.

Table 9.2

Example SLC Input Addressing (Produced Assembly)

)

Table 9.3

Example SLC Output Addressing (Consumed Assembly)

)

The example PLC program for the SLC will use the “Tripped” and
the “140M On” bit from the produced assembly and the “Fault
Reset”, “User Out A”, and “Run Fwd” bit from the consumed
assembly.

Explicit Messaging with SLC

The 1747-SDN module uses the M0 and M1 file areas for data
transfer. Only words 224 through 256 are used to execute the Explicit
Message Request and Response function. The minimum data size for
the explicit message request is 6 words and the maximum is 32
words. The following tables illustrate the standard format of the
explicit message request and response.

Table 9.4

Explicit Message Request (Get_Attribute_Single)

)

Instance 161 Default Produced Standard Distributed Motor Controller

Byte 0

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Address

I:1.23

I:1.22

I:1.21

I:1.20

I:1.19

I:1.18

I:1.17

I:1.16

Data

reserved

Reserved

reserved

Ready

Running Rev

Running Fwd

Warning

Tripped

Byte 1

Bit 15

Bit 14

Bit 13

Bit 12

Bit 11

Bit 10

Bit 9

Bit 8

Address

I:1.31

I:1.30

I:1.29

I:1.28

I:1.27

I:1.26

I:1.25

I:1.24

Data

reserved

Reserved

140M On

HOA

User In 3

User In 2

User In 1

User In 0

Instance 160 Default Consumed Standard Distributed Motor Controller

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Address

O:1.23

O:1.22

O:1.21

O:1.20

O:1.19

O:1.18

O:1.17

O:1.16

Data

User Out B

User Out A

reserved

reserved

reserved

Fault Reset

Run Rev

Run Fwd

Bit location within Word

15 … 8

7 … 0

TXID

COMMAND

Word - 0

PORT

SIZE

Word - 1

SERVICE

MAC ID

Word - 2

CLASS

Word - 3

INSTANCE

Word - 4

ATTRIBUTE

Word - 5