6-48

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

Comm Data Rate
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.

Parameter Number

203

CommNode Addr
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.

Parameter Number

204

Comm Loss Action
Selects the drive’s response to a loss of the communication connection or excessive
communication errors.
0 = Fault (Default)
Drive will fault on an F81 Comm Loss and coast to stop
1 = Coast Stop
Stops drive via coast to stop
2 = Stop
Stops via Parameter 137 (Stop Mode) setting
3 = Continu Last
Drive continues operating at communication commanded speed saved in RAM

Parameter Number

205

Related Parameters

115, 137, 206

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

3

Default Value

0

Comm Loss Time
Sets the time that the drive remain in communication loss before implanting the
option selected in Parameter 205 (Comm Loss Action).

Parameter Number

206

Related Parameters

115, 205

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 sec

Minimum Value

0.1 sec

Maximum Value

60.0 sec

Default Value

15.0 sec

Comm Format
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.

Parameter Number

207

Language
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.

Parameter Number

208

Anlg Out Setpnt
When parameter 165 (Analog Out Sel) is set to option 18, this sets the percentage of
the analog output desired

Parameter Number

209

Related Parameter

165

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1%

Minimum Value

0.0%

Maximum Value

100.0%

Default Value

0.0%