Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

5-11

➊ Reserved for Bulletin 284A units.

Starter COS Mask
This parameter allows the installer to define the change-of-state conditions that will
result in a change-of-state message being produced.

Parameter Number

19

Access Rule

GET/SET

Data Type

WORD

Group

DeviceNet

Units

Minimum Value

0

Maximum Value

16383

Default Value

16383

Bit

Function

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Tripped

X

Warning

X

Running Fwd

X

Running Rev

X

Ready

X

Net Ctl Status

X

Net Ref Status

X

At Reference

X

User Input 1

X

User Input 2

X

User Input 3

X

User Input 4

X

HOA Status

X

140M On